ABB TPU2000 Technical Manual page 286

Modbus/modbus plus/ modbus tcp/ip automation
Table of Contents

Advertisement

TPU2000/2000R Modbus/Modbus Plus/ Modbus TCP/IP Automation Guide
16
ALT1
17
ALT2
18
ECI1
19
ECI2
20
WCI
21
Trip
22
SPR
23
TCM
24
ULI1
25
ULI2
26
ULI3
27
ULI4
28
ULI5
29
ULI6
30
ULI7
31
ULI8
32
ULI9
33
CRI
Example : if message
I/O word is 00100100 00010001 hex 2411
Note the Physical Inputs are translated using the physical input table below: In the example IN3, IN10, IN8 and IN5 are
selected for GND.
The AND/OR selection and enable disable mapping is selected with commands 3 11 3 and 3 11 2
Bit
---
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Msg byte
1/1
1/2
Enables Alt 1 Settings
Enables Alt 2 Settings
Event-1 Capture Initiated
Event-2 Capture Initiated
Waveform Capture Initiated
Initiates Diff Trip Output
Sudden Pressure Input
Trip Coil Monitoring
User Logical Input 1
User Logical Input 2
User Logical Input 3
User Logical Input 4
User Logical Input 5
User Logical Input 6
User Logical Input 7
User Logical Input 8
User Logical Input 9
Clears Through Fault and OC Counters
2/1 = hex 24
2/2 = hex 11
2/3 = hex 4
Physical Input
--------------
IN6
IN7
IN8
IN2
IN9
IN3
IN4
IN5
IN1
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Definition
Relay Status
Bit 0 : SelfTest Status
Bit 1 : Contact Input Status changed
Bit 2 : Local Settings Change
Bit 3 : Remote Edit Disabled.
Bit 4 : Alternate Settings Group 1 enabled.
Bit 5 : Alternate Setting Group 2 enabled.
Bit 6 : Fault Record Logged.
Bit 7 : Power was Cycled
Command + Subcommand = 0x41
276