Physical Output Block (Two Bit Data With Momentary Change Detection): Not Available On Tpu2000; Table 5-4. Modbus Physical Output Momentary Change Detect Address Allocation - ABB TPU2000 Technical Manual

Modbus/modbus plus/ modbus tcp/ip automation
Table of Contents

Advertisement

TPU2000/2000R Modbus/Modbus Plus/ Modbus TCP/IP Automation Guide
Register
Address
3
00162
OCA-3
3
00163
PWatt3
3
00164
OCA Gnd
3
00165
Reserved
3
00166
Reserved
3
00167
Reserved
3
00168
Reserved
3
00169
Reserved
3
00170
Reserved
3
00171
Reserved
3
00172
Reserved
3
00173
Reserved
3
00174
Reserved
3
00175
Reserved
3
00176
Reserved
3= 3 Winding TPU Only
(L) = Latched or Seal In Point
Physical Output Block (Two Bit Data with Momentary Change Detection): Not available
on TPU2000
The TPU2000R allows for momentary bit change detect for all physical outputs on the protective device. The
physical output devices. The status bit will reflect the same status as that of 00257 through 00272. The
momentary bit shall detect a status change between reads of the element's data. As always, the bits must be
read in pairs for accurate reporting of the element status. Table 5-4 lists the definitions of each defined 0X
address.

Table 5-4. Modbus Physical Output Momentary Change Detect Address Allocation

Discrete
Item
Address
01025
Spare Status
01026
Spare Momentary
01027
Spare Status
01028
Spare Momentary
01029
Spare Status
01030
Spare Momentary
01031
Spare Status
01032
Spare Momentary
01033
Spare Status
01034
Spare Momentary
01035
Spare Status
01036
Spare Momentary
01037
Spare Status
01038
Spare Momentary
01039
Spare Status
01040
Spare Momentary
01041
OUT 7
01042
OUT 7
01043
OUT 6
01044
OUT 6
01045
OUT 5
01046
OUT 5
01047
OUT 4
Item
Winding 3 Overcurrent Alarm Energized
Winding 3 Positive 3 Phase kWatt Alarm Energized
Ground Overcurrent Alarm Energized
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Physical Output Contact 7
Physical Output Contact 7 Change Detect Between Scans
Physical Output Contact 6
Physical Output Contact 6 Change Detect Between Scans
Physical Output Contact 5
Physical Output Contact 5 Change Detect Between Scans
Physical Output Contact 4
Description
Description
62

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tpu2000r

Table of Contents