ABB TPU2000 Technical Manual page 296

Modbus/modbus plus/ modbus tcp/ip automation
Table of Contents

Advertisement

TPU2000/2000R Modbus/Modbus Plus/ Modbus TCP/IP Automation Guide
5 = Percent 25 Tap
6 = Percent 40 Tap
7 = User Curve 1
8 = User Curve 2
9 = User Curve 3
Mode Selection Type 87T
0 = Disabled
1 = 2nd Harmonics
2 = 2nd & 5th Harmonics
3 = All Harmonics
Msg byte
1/1
1/2
1/3
2/1
2/2
2/3
3/1
3/2
3/3
4/1
4/2
4/3
5/1
5/2
5/3
6/1
6/2
6/3
7/1
7/2
7/3
8/1
8/2
8/3
9/1
9/2
9/3
10/1
10/2
10/3
11/1
11/2
11/3
12/1
12/2
12/3
13/1
13/2
13/3
14/1
14/2
14/3
15/1
15/2
15/3
16/1
Definition
Relay Status (see command 3 4 1, msg 1/1)
Command + Subcommand = (Prim=0x48, Alt1=0x49, Alt2=0x4a)
Total Number of Messages = 25
87T Curve byte (Type 87T)
87T Minimum I Operate (0.2-1.0 *10)
87T Percent Restraint (15-60)
87T Restraint Mode (Mode Selection Type 87T)
87T 2nd Harmonic Restraint high byte(7.5-25 *10)
87T 2nd Harmonic Restraint low byte
87T 5th Harmonic Restraint high byte (15-40 *10)
87T 5th Harmonic Restraint low byte
87T All Harmonics Restraint high byte (15-40 *10)
87T All Harmonics Restraint low byte
87H Tap X byte (6-20 *10)
87T-1 Tap Amp (2-9 Amp *10, 0.4-1.8 Amp *50)
51P-1 Curve Select byte (Type I)
51P-1 Pickup Amp/OA (1-12 Amp *10, 0.2-2.4Amp *50)
51P-1 Timedial/delay (dial 1-10 *20, delay 0-10 *20)
50P-1 Curve Select byte (Type II)
50P-1 Pickup X byte (0.5-20.0, *10)
50P-1 Timedial/delay high byte (dial *10,delay *100)
50P-1 Timedial/delay low (dial 1-10, delay 0-9.99)
150P-1 Curve Select byte (Type II)
150P-1 Pickup X (0.5-20, *10)
150P-1 Timedial high byte (0-9.99, *100)
150P-1 Timedial low byte
46-1 Curve Select byte (Type I)
46-1 Pickup Amp byte (1-12 Amp *10, 0.2-2.4Amp *50)
46-1 Timedial/delay (dial 1-10 *20, delay 0-10 *20)
51N-1 Curve Select byte (Type I)
51N-1 Pickup Amp byte (1-12 Amp *10, 0.2-2.4Amp *50)
51N-1 Timedial/delay (dial 1-10 *20, delay 0-10 *20)
50N-1 Curve Select byte (Type II)
50N-1 Pickup X byte (0.5-20, *10)
50N-1 Timedial/delay high byte (dial *10,delay *100)
50N-1 Timedial/delay low (dial 1-10, delay 0-9.99)
150N-1 Curve Select byte (Type II)
150N-1 Pickup X byte (0.5-20, *10)
150N-1 Time Delay high byte (0-9.99, *100)
150N-1 Time Delay low byte
87T-2 Tap Amp byte (2-9 Amp *10, 0.4-1.8 Amp *50)
51P-2 Curve Select byte (Type I)
51P-2 Pickup Amp/OA (1-12 Amp *10, 0.2-2.4Amp *50)
51P-2 Timedial/delay (dial 1-10 *20, delay 0-10 *20)
50P-2 Curve Select byte (Type II)
50P-2 Pickup X byte (0.5-20, *10)
286

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tpu2000r

Table of Contents