ABB TPU2000 Technical Manual page 352

Modbus/modbus plus/ modbus tcp/ip automation
Table of Contents

Advertisement

TPU2000/2000R Modbus/Modbus Plus/ Modbus TCP/IP Automation Guide
Data Byte
1/1
1/2
1/3
2/1
2/2
2/3
3/1
3/2
3/3
4/1
4/2
4/3
5/1
5/2
5/3
14.1 Report Waveform Capture Settings ( 3 14 1 )
Data Byte
1/1
1/2
1/3
2/1 - 6/3
7/1
Definition
Most significant high byte of password
Most significant low byte of password
Least significant high byte of password
Least significant low byte of password
Spare
Command + Subcommand = 0xe0
Trigger source (byte 1)
Bit 0: 87T
Bit 1: 87H
Bit 2: 51P-1
Bit 3: 51N-1
Bit 4: 50P-1
Bit 5: 50N-1
Bit 6: 150P-1
Bit 7: 150N-1
Trigger source (byte 2)
Bit 0: 46-1
Bit 1: 51P-2
Bit 2: 51G-2
Bit 3: 50P-2
Bit 4: 50G-2
Bit 5: 150P-2
Bit 6: 150G-2
Bit 7: 46-2
Trigger source : (byte 3)
Bit 0: Through Fault
Bit 1: Harmonic Restraint
Bit 2: External (WCI)
Trigger source:reserved (byte 4)
Trigger position quarter cycle:
0 to 255 (for 64 qtr cycle record)
0 to 128 (for 32 qtr cycle record)
0 to 64 (for 16 qtr cycle record)
0 to 32 (for 8 qtr cycle record)
Mode/Record Size
bit 0, 1: 00 = 8 rec of 8 qtr cycle record
01 = 4 rec of 16 qtr cycle record
10 = 2 rec of 32 qtr cycle record
11 = 1 rec of 64 qtr cycle record
bit 6:
Single Shot Mode (0=Off, 1=On)
bit 7:
Append Record Mode (0=Off, 1=On)
Spare
Checksum high byte
Checksum low byte
Definition
Relay Status (see command 3 4 1, msg 1/1)
Command + Subcommand = 0xe1
Total Number of Messages = 9
Unit ID Name (15 characters)
Trigger source (byte 1)
Bit 0: 87T
Bit 1: 87H
Bit 2: 51P-1
Bit 3: 51N-1
342