ABB TPU2000 Technical Manual page 353

Modbus/modbus plus/ modbus tcp/ip automation
Table of Contents

Advertisement

7/2
7/3
8/1
8/2
8/3
TPU2000/2000R Modbus/Modbus Plus Automation Guide
Bit 4: 50P-1
Bit 5: 50N-1
Bit 6: 150P-1
Bit 7: 150N-1
Trigger source (byte 2)
Bit 0: 46-1
Bit 1: 51P-2
Bit 2: 51G-2
Bit 3: 50P-2
Bit 4: 50G-2
Bit 5: 150P-2
Bit 6: 150G-2
Bit 7: 46-2
Trigger source (byte 3)
Bit 0: Through Fault
Bit 1: Harmonic Restraint
Bit 2: External (WCI)
Trigger source (byte 4)
Trigger position quarter cycle:
0 to 255 (for 64 qtr cycle record)
0 to 128 (for 32 qtr cycle record)
0 to 64 (for 16 qtr cycle record)
0 to 32 (for 8 qtr cycle record)
Mode/Record Size