ABB TPU2000 Technical Manual page 139

Modbus/modbus plus/ modbus tcp/ip automation
Table of Contents

Advertisement

Register
Address
42564
Setting At Fault Event
42565
Fault Record Number
42566
Year
42567
Month
42568
Day
42569
Hour
42570
Minute
42571
Second
42572
Hundredths of Seconds 0 - 99
42573
Winding3 Tap
42574
I restraint Phase A-Winding 3
42575
I restraint Phase B-Winding 3
42576
I restraint Phase C-Winding 3
42577
2nd Harmonic Phase A-Winding 3
42578
5th Harmonic Phase A-Winding 3
42579
All Harmonic Phase A-Winding 3
42580
2nd Harmonic Phase B-Winding 3
42581
5th Harmonic Phase B-Winding 3
42582
All Harmonic Phase B-Winding 3
42583
2nd Harmonic Phase C-Winding 3
42584
5th Harmonic Phase C-Winding 3
42585
All Harmonic Phase C-Winding 3
42586
I restraint Phase A-Winding 3 (Ang)
42587
I restraint Phase B-Winding 3 (Ang)
42588
I restraint Phase C-Winding 3 (Ang)
42589
Winding 3 Tap
42590
I restraint Phase A-Winding 3 (Ang)
42591
I restraint Phase B-Winding 3 (Ang)
42592
I restraint Phase C-Winding 3 (Ang)
42593
2nd Harmonic Phase A-Winding 3
42594
5th Harmonic Phase A-Winding 3
42595
All Harmonic Phase A-Winding 3
42596
2nd Harmonic Phase B-Winding 3
42597
5th Harmonic Phase B-Winding 3
TPU2000/2000R Modbus/Modbus Plus Automation Guide
Item
2 digit 00 -99
1 - 12
1 - 31
00 - 23
00 - 59
00 - 59
Description (Multiplier if any)
03= 51P-2 – Winding 2 Phase Time Overcurrent
st
04 = 50P-1 – 1
Winding 1 Phase Inst. Overcurrent
st
05 = 50N-1 – 1
Winding 1 Neutral Inst. Overcurrent
nd
06 = 150P-1 – 2
Winding 1 Phase Inst. Overcurrent
nd
07 =150N-1– 2
Winding 1 Neutral Inst. Overcurrent
08 = 46-1 – Neg. Sequence 1 Inst. Time Overcurrent
09 = 51P-2 – Winding 2 Phase Time Overcurrent
10 = 51G-2 – Winding 2 Ground Time Overcurrent
st
11 = 50P-2– 1
Winding 2 Phase Inst. Overcurrent
st
12 =50G-2 – 1
Winding 2 Ground Inst. Overcurrent
nd
13 = 150P-2 – 2
Winding 2 Phase Inst. Overcurrent
nd
14 = 150G-2 – 2
Winding 2 Ground Inst. Overcurrent
15 = 46-2 – Neg. Sequence 2 Inst. Time Overcurrent
16 = ECI-1 – Event Capture Initiate 1
17 = ECI-2 – Event Capture Initiate 2
18 = Through Fault
19 = Harmonic Restraint
Unsigned 16 Bit
01 = Primary Settings
02 = Alternate 1 Settings
03 = Alternate 2 Settings
Unsigned 16 Bit
(1 – 999, only last 32 kept)
Unsigned 16 Bit Year of Fault
Unsigned 16 Bit Month of Fault
Unsigned 16 Bit Day of Fault
Unsigned 16 Bit Hour of Fault
Unsigned 16 Bit Minute of Fault
Unsigned 16 Bit Second of Fault
Unsigned 16 Bit Hundredth Second of Fault Time
Unsigned 16 Bit (X 10)
Unsigned 16 Bit (X 800)
Unsigned 16 Bit (X 800)
Unsigned 16 Bit (X 800)
Unsigned 16 Bit (X 2)
Unsigned 16 Bit (X 2)
Unsigned 16 Bit (X 2)
Unsigned 16 Bit (X 2)
Unsigned 16 Bit (X 2)
Unsigned 16 Bit (X 2)
Unsigned 16 Bit (X 2)
Unsigned 16 Bit (X 2)
Unsigned 16 Bit (X 2)
Unsigned 16 Bit
Unsigned 16 Bit
Unsigned 16 Bit
Unsigned 16 Bit (X 10)
Unsigned 16 Bit
Unsigned 16 Bit
Unsigned 16 Bit
Unsigned 16 Bit (X 2)
Unsigned 16 Bit (X 2)
Unsigned 16 Bit (X 2)
Unsigned 16 Bit (X 2)
Unsigned 16 Bit (X 2)
129

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tpu2000r