ABB TPU2000 Technical Manual page 333

Modbus/modbus plus/ modbus tcp/ip automation
Table of Contents

Advertisement

0
not used reserved for fixed DIFF TRIP
1
Contact OUT5
2
Contact OUT7
3
Contact OUT4
4
Contact OUT6
5
Contact OUT3
6
Contact OUT2
7
Contact OUT1
8
spare
9
spare
10
spare
11
spare
12
spare
13
spare
14
spare
15
spare
11.7 Receive Programmable Output User Defined Names (3 11 7)
User definable 8 char output strings. Byte 9 is an implied NULL.
Msg byte
1/1
1/2
1/3
2/1
2/2
2/3
3/1-5/2
5/3-8/1
8/2-10/3
11/1-13/2
13/3-16/1
16/2-18/3
19/1-21/2
21/3-24/1
24/2-26/3
27/1-29/2
29/3-32/1
32/2-34/3
35/1-37/2
37/3-40/1
40/2
40/3
11.8,9,10 Receive Relay Settings ( 3 11 X )
( 3 11 8 ) = Primary Settings
( 3 11 9 ) = Alternate 1 Settings
( 3 11 10 ) = Alternate 2 Settings
Low byte consists of bits 0 through 7.
High byte consists of bits 8 through 15.
Curve Selection Type I
0 = Extremely Inverse
1 = Very Inverse
2 = Inverse
3 = Short Time Inverse
4 = Definite Time
TPU2000/2000R Modbus/Modbus Plus Automation Guide
Definition
Most significant high byte of password
Most significant low byte of password
Least significant high byte of password
Least significant low byte of password
spare
Command + Subcommand = 0xb7
OUT1 Character String 8 bytes
OUT2 Character String 8 bytes
OUT3 Character String 8 bytes
OUT4 Character String 8 bytes
OUT5 Character String 8 bytes
OUT6 Character String 8 bytes
OUT7 Character String 8 bytes
spare Character String 8 bytes
spare Character String 8 bytes
spare Character String 8 bytes
spare Character String 8 bytes
spare Character String 8 bytes
spare Character String 8 bytes
spare Character String 8 bytes
Checksum high byte
Checksum low byte
323