Figure 5-55. Mapping Function Screen For Logical Inputs - ABB TPU2000 Technical Manual

Modbus/modbus plus/ modbus tcp/ip automation
Table of Contents

Advertisement

TPU2000/2000R Modbus/Modbus Plus/ Modbus TCP/IP Automation Guide
FLI 11
Phase Instantaneous Level 2
Enable Winding 1
FLI 12
Phase Instantaneous Level 2
Enable Winding 2
FLI 13
Neutral Instantaneous Level 2
Enable Winding 1
FLI 14
Ground Instantaneous Level 2
Enable Winding 2
FLI 15
Winding 1 Negative Sequence
Control
FLI 16
Winding 2 Negative Sequence
Control
The usefulness of this feature cannot be understated. Each one of these functions can be forced via a network
control. Programming need not be done to allow for function control via a network. If the relaying feature
"Waveform Capture Initiate" were to be enabled, the bit FLI 21 could be forced to an "ON" condition via the
network control. If a desired control function were to be controlled via the network, then ECP mapping would
have to be configured as per Figure 5-55. The method employed to force the state of the function is similar to that
of the Group II and III functions. As illustrated in Table 5-48, the mapping of each of the FLI's is illustrated.
Registers 41430 through 41439 allow forcing of the desired feature.
Group IV functions operate as follows:
Register 41434 = Force Physical Output Change Mask - Selects Control for FLI 17 – FLI 32
Register 41435 = Force Physical Output Change Mask - Selects Control for FLI 01 – FLI 16
Register 41436 = Force Physical Output Normal State Mask - Places FLI 17 – FLI 32 in Normal or Force Mode
Register 41437 = Force Physical Output Normal State Mask - Places FLI 01 – FLI 16 in Normal or Force Mode
Register 41438 = Physical Output Forcing State Mask – If Bit is in Force Mode, Determines Force State FLI 17 to
FLI 32 (State 1 = energized State 0 = de-energized)
Register 41439 = Physical Output Forcing State Mask – If Bit is in Force Mode, Determines Force State FLI 01 to
FLI 16 (State 1 = energized State 0 = de-energized)

Figure 5-55. Mapping Function Screen for Logical Inputs

150P-1
FLI 27
User Logical Input 3
150P-2
FLI 28
User Logical Input 4
150N-1
FLI 29
User Logical Input 5
150G-2
FLI 30
User Logical Input 6
46-1
FLI 31
User Logical Input 7
46-2
FLI 32
User Logical Input 8
ULI 3
ULI 4
ULI 5
ULI 6
ULI 7
ULI 8
148