11.13 Receive Alarm Settings ( 3 11 13 )
Low byte consists of bits 0 through 7.
High byte consists of bits 8 through 15.
Msg byte
1/1
1/2
1/3
2/1
2/2
2/3
3/1
3/2
3/2
4/1
4/2
4/3
5/1
5/2
5/3
6/1
6/2
6/3
7/1
7/2
7/3
8/1
8/2
8/3
9/1
9/2
9/3
10/1
10/2
10/3
11/1
11/2
spare
Command + Subcommand = 0xbc
Through Faults Counter high byte (0-9999)
Through Faults Counter low byte
Thr Fault Sum kAmp A Counter high byte (0-9999)
Thr Fault Sum kAmp A Counter low byte
Through Fault Sum Cyc Counter high byte (0-99990)
Through Fault Sum Cyc Counter low byte
Overcurrent Trips Counter high byte (0-9999)
Overcurrent Trips Counter low byte
Differential Trips Counter high byte (0-9999)
Differential Trips Counter low byte
Thr Fault Sum kAmp B Counter high byte (0-9999)
Thr Fault Sum kAmp B Counter low byte
Thr Fault Sum kAmp C Counter high byte (0-9999)
Thr Fault Sum kAmp C Counter low byte
Spare
Spare
Checksum high byte
Checksum low byte
Definition
Most significant high byte of password
Most significant low byte of password
Least significant high byte of password
Least significant low byte of password
spare
Command + Subcommand = 0xbd
Through Faults Alarm Threshold high byte (0-9999)
Through Faults Alarm Threshold low byte
Through Fault Sum kAmp Alarm Thres high (0-9999)
Through Fault Sum kAmp Alarm Threshold low byte
Through Fault Sum Cyc Alarm high (0-99990, /10)
Through Fault Sum Cyc Alarm Threshold low byte
Overcurrent Trips Alarm high byte (0-9999)
Overcurrent Trips Alarm low byte
Differential Trips Alarm high byte (0-9999)
Differential Trips Alarm low byte
Phase Demand Alarm high byte (1-9999)
Phase Demand Alarm low byte
Neutral Demand Alarm high byte (1-9999)
Neutral Demand Alarm low byte
Load Alarm high byte (1-9999)
Load Alarm low byte
Phase Demand Alarm high byte (1-9999,10000=Disables)
Phase Demand Alarm low byte
Low PF Alarm high byte(0.5-1.0 *100, 101=Disables)
Low PF Alarm low byte
High PF Alarm high byte(0.5-1.0 *100, 101=Disables)
High Pf Alarm low byte
Positive kVAR Alarm high byte (10-99990 / 10,10000=Disable)
Positive kVAR Alarm low byte
Negative kVAR Alarm high byte (10-99990 /10,10000=Disable)
Negative kVAR Alarm high byte