Figure 5-12. Modbus Plus Path Designation; Figure 5-13. Modbus Plus Addressing Example - ABB TPU2000 Technical Manual

Modbus/modbus plus/ modbus tcp/ip automation
Table of Contents

Advertisement

TPU2000/2000R Modbus/Modbus Plus/ Modbus TCP/IP Automation Guide
8 Program Master Paths
8 Data Slave Paths
The TPU2000R implementation of Modbus Plus shows the data path implementation. The TPU2000R Modbus
Plus implementation allows:
The TPU2000R to receive information requests from a device acting as a host along one of its 8 data
slave paths.
The TPU2000R to place up to 32 registers of data on the Global Out Data Path. The data sent on the
Global Out Path is configurable through ECP or WinECP. The Configuration Method is described in
Section 4.
The TPU2000R implements Modbus Plus as a HOST device. The Modbus Plus address assignment required
depends upon the understanding of the path assignment discussion. Figure 5-13 illustrates the addressing
required when a device (such as a programmable logic controller or a host device with a Modbus Plus SA 85
card) must access a TPU2000R via Modbus Plus. An application note is included in Appendix C describing the
process for Programmable Logic Controller attachment with a TPU2000R. This application note can easily be
applied in connecting a TPU2000R to a Programmable Logic Controller Network.
As per Figure 5-13, if a host device X is to request data from an ABB TPU2000R, the node address (configured
via the front panel interface, ECP, or WinECP) is the first address node entry in the data path for the address
Routing Path 1. In the case with the nodes sharing the same network, the Routing Path 2 entry is the slave path
address communicated with. The Route address for the slave path is 1 through 8.
Routing Addr 1
Routing Addr 2
5
Bridge
8 Program Slave Paths
Modbus Plus Node
(Maximum Implementation)
8 Data Master Paths
Global Data Read

Figure 5-12. Modbus Plus Path Designation

Routing Addr 3
1
0
64 Nodes Maximum with 6000' of cable
2
12
22 32
31
30
3
X
Segment 1
Segment 2
1500 '
Repeater
1500'
12
3 4
5
6
27
28
W
1
NETWORK 2
64
1500 '
Repeater
1500'
33
From X (Host) to Q (DPU 2000R) = Same network = 28.A.0.0.0
From X (Host) to Z = Thru Networks = 1.22.A.0.0
N
From X(Host) to N = Thru Networks = 1.1.33.A.0
From W (Host) to Z = Thru Networks = 1.12.A.0.0
(NOTE A = Slave Path Number from 1 to 8)

Figure 5-13. Modbus Plus Addressing Example

8 Data Slave Paths
Global Data Write
Routing Addr 4
0
34
52
53
29
28
35
7
Q
Segment 3
Repeater
1500 '
Repeater
Z
29
21 22
23
24
25 26
Repeater
1500 '
Repeater
E C
Global Data Out
Routing Addr 5
0
8
9
NETWORK 1
Segment 4
1
1500 '
42
52
64
Bridge
= Line Termination
1500 '
44