Table 5-38. 3 Winding Harmonic Fault Register Definitions - ABB TPU2000 Technical Manual

Modbus/modbus plus/ modbus tcp/ip automation
Table of Contents

Advertisement

TPU2000/2000R Modbus/Modbus Plus/ Modbus TCP/IP Automation Guide
Register
Address
41976
I Restraint Phase A-Winding 2
41977
I Restraint Phase B-Winding 2
41978
I Restraint Phase C-Winding 2
41979
2nd Harmonic Phase A-Winding 1
41980
5th Harmonic Phase A-Winding 1
41981
All Harmonic Phase A-Winding 1
41982
2nd Harmonic Phase B-Winding 1
41983
5th Harmonic Phase B-Winding 1
41984
All Harmonic Phase B-Winding 1
41985
2nd Harmonic Phase C-Winding 1
41986
5th Harmonic Phase C-Winding 1
41987
5th Harmonic Phase C-Winding 1
41988
5th Harmonic Phase C-Winding 1
41989
5th Harmonic Phase C-Winding 1
41990
5th Harmonic Phase C-Winding 1
41991
5th Harmonic Phase C-Winding 1
41992
5th Harmonic Phase C-Winding 1
41993
5th Harmonic Phase C-Winding 1
41994
All Harmonic Phase C-Winding 1
41995
2nd Harmonic Phase A-Winding 2
41996
5th Harmonic Phase A-Winding 2
41997
All Harmonic Phase A-Winding 2
41998
2nd Harmonic Phase B-Winding 2
41999
5th Harmonic Phase B-Winding 2
42000
All Harmonic Phase B-Winding 2
42001
2nd Harmonic Phase C-Winding 2
42002
5th Harmonic Phase C-Winding 2
42003
All Harmonic Phase C-Winding 2
42004
I restraint Phase A-Winding 1 (Ang)
42005
I restraint Phase B-Winding 1 (Ang)
42006
I restraint Phase C-Winding 1 (Ang)
42007
I restraint Phase A-Winding 2 (Ang)
42008
I restraint Phase B-Winding 2 (Ang)
42009
I restraint Phase C-Winding 2 (Ang)
The 3 Winding Harmonic Fault Register Definition Table follows.

Table 5-38. 3 Winding Harmonic Fault Register Definitions

Register
Address
42561
Harmonic 3 Winding Fault Control
Register
1 = First Record
2 = Next Record
3 = Oldest Unreported Record
42562
Parameter Flag
42563
Fault Type Element
Item
Item
Description (Multiplier if any)
Unsigned 16 Bit (X 800)
Unsigned 16 Bit (X 800)
Unsigned 16 Bit (X 800)
Unsigned 16 Bit (X 2)
Unsigned 16 Bit (X 2)
Unsigned 16 Bit (X 2)
Unsigned 16 Bit (X 2)
Unsigned 16 Bit (X 2)
Unsigned 16 Bit (X 2)
Unsigned 16 Bit (X 2)
Unsigned 16 Bit (X 2)
Unsigned 16 Bit (X 2)
Unsigned 16 Bit (X 2)
Unsigned 16 Bit (X 2)
Unsigned 16 Bit (X 2)
Unsigned 16 Bit (X 2)
Unsigned 16 Bit (X 2)
Unsigned 16 Bit (X 2)
Unsigned 16 Bit (X 2)
Unsigned 16 Bit (X 2)
Unsigned 16 Bit (X 2)
Unsigned 16 Bit (X 2)
Unsigned 16 Bit (X 2)
Unsigned 16 Bit (X 2)
Unsigned 16 Bit (X 2)
Unsigned 16 Bit (X 2)
Unsigned 16 Bit (X 2)
Unsigned 16 Bit (X 2)
Unsigned 16 Bit
Unsigned 16 Bit
Unsigned 16 Bit
Unsigned 16 Bit
Unsigned 16 Bit
Unsigned 16 Bit
Description (Multiplier if any)
Fault Record Control Register
Unsigned 16 Bit
1 = Fill 42562 through 42604 with First Record in Data
Buffer.
2 = Fill 42562 through 42604 with next Record Data
pointed to in buffer.
3 = Fill 42562 through 42604 with the last (oldest
unreported) record of data.
Unsigned Integer 16 Bit
Unsigned 16 Bit
00 = 87T – % Differential Alarm
01 = 87H – High Set Inst. Differential Alarm
02 = 51P-1 – Winding 1 Phase Time Overcurrent
128