ABB TPU2000 Technical Manual page 355

Modbus/modbus plus/ modbus tcp/ip automation
Table of Contents

Advertisement

2/2
2/3
3/1
3/2
3/3
4/1
4/2
4/3
5/1
5/2
5/3
6/1
6/2
6/3
7/1
7/2
7/3
8/1 - 13/1
13/2 - 18/2
18/3 - 23/3
24/1 - 29/1
29/2 - 34/2
34/3 - 39/3
40/1 - 45/1
45/2
45/3
14.6 Fetch Next Block of a Record-Part A ( 3 14 6 )
Same message format as ( 3 14 5 )
14.7 Retransmit Last Block of a Record-Part A ( 3 14 7 )
Same message format as ( 3 14 5 )
14.8 Fetch First Block of a Record-Part B ( 3 14 8 )
Msg Byte
1/1
1/2
1/3
2/1
2/2
2/3
3/1
3/2
3/3
4/1
4/2
4/3
5/1
5/2
5/3
6/1
6/2
TPU2000/2000R Modbus/Modbus Plus Automation Guide
Block number
Sample 0: Ia-1 (high byte)
Sample 0: Ia-1 (low byte)
Sample 0: Ib-1 (high byte)
Sample 0: Ib-1 (low byte)
Sample 0: Ic-1 (high byte)
Sample 0: Ic-1 (low byte)
Sample 0: In-1 (high byte)
Sample 0: In-1 (low byte)
Sample 0: Ia-2 (high byte)
Sample 0: Ia-2 (low byte)
Sample 0: Ib-2 (high byte)
Sample 0: Ib-2 (low byte)
Sample 0: Ic-2 (high byte)
Sample 0: Ic-2 (low byte)
Sample 0: Ig-2 (high byte)
Sample 0: Ig-2 (low byte)
Sample 1 data
Sample 2 data
Sample 3 data
Sample 4 data
Sample 5 data
Sample 6 data
Sample 7 data
Spare
Spare
Definition
Relay status (see command 3 4 1, msg 1/1)
Command + Subcommand = 0xe8
Total Number of Messages = 9
Record number
Block number
Phase scale Wdg 1 (high byte)
Phase scale Wdg 1 (low byte)
Neutral scale Wdg 1 (high byte)
Neutral scale Wdg 1 (low byte)
Phase scale Wdg 2 (high byte)
Phase scale Wdg 2 (low byte)
Ground scale Wdg 2 (high byte)
Ground scale Wdg 2 (low byte)
Input status (high byte)
Input status (low byte)
Output status (high byte)
Output status (low byte)
Bit 0: Differential Trip
Bit 1: Trip failure
Bit 2: Through Fault
Bit 3: 2nd Harmonic Restraint
345