Table 5-35. 2 Winding Through Fault Register Definition For The Tpu2000/Tpu2000R - ABB TPU2000 Technical Manual

Modbus/modbus plus/ modbus tcp/ip automation
Table of Contents

Advertisement

TPU2000/2000R Modbus/Modbus Plus/ Modbus TCP/IP Automation Guide
Thirty two through faults are stored within the TPU2000/2000R. A through-fault is stored on any overcurrent trip
output or whenever the Disturbance-2 pickup setting is exceeded. Within the TPU2000 and TPU2000R the two
Winding Through Fault buffer described in Table 5-35 allows the user to obtain the fault information. In a
TPU2000R Three Winding Unit, additional fault information may be retrieved describing the fault conditions for the
third winding.
Through Fault Record Layout (TPU2000/TPU2000R)
Figure 5-41. Event Record Access Illustration of Function 23 is Issued to a TPU2000/2000R

Table 5-35. 2 Winding Through Fault Register Definition for the TPU2000/TPU2000R

Register
Address
41793
2 Winding Through Fault
Control Register
1 = First Record
2 = Next Record
3 = Oldest Unreported Record
41794
Parameter Flag
41795
Fault Type Element
Data Control Register
Through Fault Data
TPU 2000 and
TPU 2000R
E C
Data Control Register
Through Fault
Data TPU 2000R
Only (3 Winding)
Item
Fault Record Control Register
Unsigned 16 Bit
1 = Fill 41794 through 41830 with First Record in Data Buffer.
2 = Fill 41794 through 41830 with next Record Data pointed
to in buffer.
3 = Fill 41794 through 41830 with the last (oldest unreported)
record of data.
Unsigned Integer 16 Bit
Unsigned 16 Bit
00 = 87T – % Differential Alarm
01 = 87H – High Set Inst. Differential Alarm
02 = 51P-1 – Winding 1 Phase Time Overcurrent
03 = 51P-2 – Winding 2 Phase Time Overcurrent
04 = 50P-1 – 1
05 = 50N-1 – 1
06 = 150P-1 – 2
07 = 150N-1 – 2
08 = 46-1 – Neg. Sequence 1 Inst. Time Overcurrent
09 = 51P-2 – Winding 2 Phase Time Overcurrent
10 = 51G-2 – Winding 2 Ground Time Overcurrent
11 = 50P-2 – 1
12 = 50G-2 – 1
13 = 150P-2– 2
14 = 150G-2– 2
15 = 46-2 – Neg. Sequence 2 Inst. Time Overcurrent
16 = ECI-1 – Event Capture Initiate 1
41793
41794
41830
Fault Stack
42433
42434
42466
Fault Stack
Device
Description (Multiplier if any)
st
Winding 1 Phase Inst. Overcurrent
st
Winding 1 Neutral Inst. Overcurrent
nd
Winding 1 Phase Inst. Overcurrent
nd
Winding 1 Neutral Inst. Overcurrent
st
Winding 2 Phase Inst. Overcurrent
st
Winding 2 Ground Inst. Overcurrent
nd
Winding 2 Phase Inst. Overcurrent
nd
Winding 2 Ground Inst. Overcurrent
Through Fault
32 Faults in Stack Max..
Third Winding
Through Fault
Data
32 Faults in Stack Max.