2.4.1 Required installation space, IRC5 Controller

2.4 On-site installation

2.4.1 Required installation space, IRC5 Controller
Dimensions
The following illustration shows the required installation space for the IRC5 Compact
controller.
xx0900000450
a)
38
Not required if the controller is rack-mounted
A free space of 50mm on both left and right hand side of the controller is
required if the controller is mounted on desk (not rack-mounted).
A free space of 100 mm on the backside of the controller is required to ensure
proper cooling. Do not place customer cables over the fan cover on the
backside of the controller (makes difficult to inspect and leads to inefficient
cooling).