Siemens 6RA7086-6KS22 Operating Instructions Manual page 157

6ra70 series, microprocessor-based converters from 6kw to 2500kw for variable-speed dc drives, simoreg dc master
Table of Contents

Advertisement

05.05
Binary inputs (see also Section 8, sheet G111)
Module C98043-A7006 CUD2
Function
Supply
Ground digital M
Select input
binary 3
Select input
binary 4
Select input
binary 5
Select input
binary 6
Binary outputs (see also Section 8, sheet G112)
Module C98043-A7006 CUD2
Function
Select output
binary 3
Ground M
Select output
binary 4
Ground M
Serial interface 3 RS485 (G-SST3)
Module C98043-A7006 CUD2
Function
Terminal
TX+
TX-
RX+/TX+
RX-/TX-
M
For transmission rate =187.5kBd ⇒ 600m
Cable length:
For transmission rate ≤ 93.75kBd ⇒ 1200m
The following must be observed: DIN 19245 Part 1
The potential difference between the data reference potentials M of all interfaces must not
exceed -7V / +12V. If this cannot be guaranteed, then equipotential bonding must be
provided.
Activate interface 3:
– Set the baud rate in parameter P803.
– Set the protocol in parameter P800.
Siemens AG
6RX1700-0AD76
SIMOREG DC Master
Operating Instructions
Terminal
X163
44
45
40
41
42
43
Terminal
X163
50
51
52
53
Connection values/Remarks
X162
61
RS485, 4-wire send cable, positive differential output
61
RS485, 4-wire send cable, negative differential output
63
RS485, 4-wire receive cable, positive differential input,
2-wire send/receive cable, positive differential input
64
RS485, 4-wire receive cable, negative differential input,
2-wire send/receive cable, negative differential input
65
Ground
Connection values/Remarks
24V DC, short circuit proof
max. load 200mA (terminals 34, 44, and 210 combined),
internal supply with respect to internal ground
Overload response: Error signal F018
Warning signal A018
H signal: +13V to +33V
L signal: – 33V to +3V or terminal open
8.5mA at 24V
Connection values/Remarks
H signal: +20V to +26V
L signal: 0 to +2V
Short-circuit-proof 100mA
Overload response: Error signal F018
Warning signal A018
Internal snubber circuit (free-wheeling diode)
Connections
6-71

Hide quick links:

Advertisement

Table of Contents
loading