Siemens 6RA7086-6KS22 Operating Instructions Manual page 636

6ra70 series, microprocessor-based converters from 6kw to 2500kw for variable-speed dc drives, simoreg dc master
Table of Contents

Advertisement

Parameter list
PNU
Description
U807
Telegram failure time on paralleling interface
(2807)
0
0.001...65.000 Permissible time interval between two data exchange
(G195)
Fault message F014 is displayed if no data are exchanged with the parallel-
connected converter within this delay period.
The monitoring function is implemented within a 20 ms cycle. For this
reason, only setting values which constitute a multiple of 20 ms are
meaningful.
Note:
The telegram monitoring function is active
from the receipt of the first error-free telegram after connection of the
electronics power supply
from the receipt of the first error-free telegram after the telegram monitor
has responded (i.e. monitoring timeout).
U808
Source for triggering of message F014
(2808)
Selection of binector which must trigger message F014 when it switches to
*
log. "1"
(G195)
6040 = binector B6040
6041 = binector B6041
n809
Diagnostic information for paralleling interface
(2809)
i001 to i009 = Free-running counter, overflow at 65535
(G195)
i001:
Number of error-free telegrams
i002:
Number of errored telegrams
i003:
Transmit Error Counter
i004:
Receive Error Counter
i005:
Phase Error Counter
i006:
Baud rate Error Counter
i007:
Bad BCC Counter
i008:
Timeout Counter
i009:
Number of telegrams with unknown identifier
11-172
No time monitoring
operations before a fault message is output.
Value range
No. indices
[Unit]
Factory
Steps
setting
Type
0.000 to 65.000
Ind: None
[s]
FS=0.100
0.001s
Type: O2
6040, 6041
Ind: None
FS=6040
Type: L2
0 to 65535
Ind: 9
Type: O2
SIEMENS AG
SIMOREG DC Master
Operating Instructions
05.05
See
Change
(Access /
Status)
P052 = 3
P051 = 40
Online
P052 = 3
P051 = 40
Offline
P052 ≥ 0
6RX1700-0AD76