Siemens 6RA7086-6KS22 Operating Instructions Manual page 211

6ra70 series, microprocessor-based converters from 6kw to 2500kw for variable-speed dc drives, simoreg dc master
Table of Contents

Advertisement

05.05
n732.027
or
n732.059
n732.028
or
n732.060
n732.029
or
n732.061
Fault and alarm messages:
For details about fault messages, see Section 10.
Fault F080
An error occurred as board CBD was being initialized, e.g. incorrect value of a CB
parameter, incorrect bus address or defective board.
Fault F081
The heartbeat counter (counter on CBD) which is monitored by SIMOREG for "signs of life"
from the board has not changed for at least 800 ms.
Fault F082
Failure of PZD telegrams or a fault in the transmission channel.
Alarm A081
Idle condition alarm; a PZD telegram of length = 0 has been received either in the "poll" or
"bit strobe I/O message channel". The alarm is reset when a PZD telegram of normal length
is received.
Faulty CAN messages of this type are ignored. The last transmitted data remain valid.
Alarm A083 (error alarm)
Telegrams containing errors are being received or transmitted and the error counter on the
supplementary board has exceeded the alarm limit.
The faulty telegrams are ignored. The last transmitted data remain valid. If the faulty
telegrams contain process data, fault message F082 with fault value 10 may be generated
as a function of the telegram failure time set in U722.
Alarm A084
Faulty DeviceNet CAN telegrams have been received or transmitted, causing the internal
error counter to overrun.
Faulty CAN messages of this type are ignored. The last transmitted data remain valid.
SIEMENS AG
6RX1700-0AD76
SIMOREG DC Master
Operating Instructions
Value
Software identifier
(extended software version identifier, see also r065)
Date of generation of CBD software (day and month)
th
(e.g. "2508" = 25
Date of generation of CBD software (year)
Meaning
August)
Start-Up
7-53