Requirements For Operating The Cbc With Canopen - Siemens 6RA7086-6KS22 Operating Instructions Manual

6ra70 series, microprocessor-based converters from 6kw to 2500kw for variable-speed dc drives, simoreg dc master
Table of Contents

Advertisement

Start-Up

7.7.3.2.3 Requirements for operating the CBC with CANopen

To be able to operate the CBC with CANopen, the following two conditions must be fulfilled:
SIMOREG firmware, V1.9 and later
-
CBC firmware, V2.2 and later
-
To be able to operate the individual CANopen profiles, certain parameter settings must be made in
the SIMOREG.
7.7.3.3
Diagnostic tools:
LED displays on the CBC (flashing LEDs indicate normal operation):
Red LED
Yellow LED
Green LED
red
flashing
flashing
flashing
flashing
flashing
7-36
Status of CBC
Communication between SIMOREG and CBC
Communication between CBC and CAN Bus
LED
yellow
green
flashing
flashing
Normal operation
off
on
CBC waiting for commencement of initialization by SIMOREG
on
off
CBC waiting for end of initialization by SIMOREG
flashing
off
No PZD data exchange via CAN Bus
on
on
CBC defective
Status
SIEMENS AG
SIMOREG DC Master
Operating Instructions
05.05
6RX1700-0AD76

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents