Siemens 6RA7086-6KS22 Operating Instructions Manual page 539

6ra70 series, microprocessor-based converters from 6kw to 2500kw for variable-speed dc drives, simoreg dc master
Table of Contents

Advertisement

05.05
PNU
Description
P701
Normalization of "Main setpoint" analog input
This parameter specifies the percentage value which is generated for an
FDS
input voltage of 10V (or an input current of 20mA) at the analog input.
The following generally applies:
(G113)
For voltage input:
[%] =
P
701
10
V
With current input:
[%] =
P
701
20
mA
P702
Offset for "Main setpoint" analog input
(G113)
P703
Mode of signal injection at "Main setpoint" analog input
*
0 = Injection of signal with sign
1 = Injection of absolute value of signal
(G113)
2 = Injection of signal with sign, inverted
3 = Injection of absolute value of signal, inverted
P704
Source for selection of sign reversal at "Main setpoint" analog input
*
Selection of binector to control sign reversal at the analog input ("1" state
= reverse sign)
(G113)
0 = binector B0000
1 = binector B0001
etc.
P705
Filtering time for "Main setpoint" analog input
Note: Hardware filtering of approximately 1 ms is applied as standard.
(G113)
P706
Source for enabling of "Main setpoint" analog input
*
Selection of binector to control enabling of the analog input ("1" state =
enabled)
(G113)
0 = binector B0000
1 = binector B0001
etc.
SIEMENS AG
6RX1700-0AD76
SIMOREG DC Master
Operating Instructions
Y
X .. Input voltage in volts
X
Y .. % value which is generated for input
voltage X
Y
X .. Input current in mA
X
Y .. % value which is generated for input
current X
Value range
No. indices
[Unit]
Factory
Steps
setting
Type
-1000.0 to 1000.0
Ind: 4
[%]
FS=100.0
0.1%
Type: I2
-200.00 to 199.99
Ind: None
[%]
FS=0.00
0.01%
Type: I2
0 to 3
Ind: None
1
FS=0
Type: O2
All binector numbers
Ind: None
1
FS=0
Type: L2
0 to 10000
Ind: None
[ms]
FS=0
1ms
Type: O2
All binector numbers
Ind: None
1
FS=1
Type: L2
Parameter list
See
Change
(Access /
Status)
P052 = 3
P051 = 40
Online
P052 = 3
P051 = 40
Online
P052 = 3
P051 = 40
Offline
P052 = 3
P051 = 40
Offline
P052 = 3
P051 = 40
Online
P052 = 3
P051 = 40
Offline