Siemens 6RA7086-6KS22 Operating Instructions Manual page 607

6ra70 series, microprocessor-based converters from 6kw to 2500kw for variable-speed dc drives, simoreg dc master
Table of Contents

Advertisement

05.05
PNU
Description
Technology controller: Control bits
U500
Source for technology controller enabling command
(2500)
0 = binector B0000
*
1 = binector B0001
S00
etc.
(B170)
U502
PI/PID controller switchover
(2502)
0
PI controller (D component is applied only in actual-value
*
channel)
S00
1
PID controller (D component is applied for control deviation)
FDS
(B170)
U503
Set P component to zero
(2503)
0
Set controller P component to zero (i.e. to obtain pure I
*
controller)
S00
1
Controller P component is active
FDS
(B170)
U504
Set I component to zero
(2504)
0
Set controller I component to zero (i.e. to obtain pure P
*
controller)
S00
1
Controller I component is active
FDS
(B170)
Technology controller: Set I component
When the state of the binector selected in U506 switches from log. "0" to "1", the I component of the technology controller is set to the
value parameterized in U505.
With this function it is possible, for example, to use the same signal (binector) to control controller enabling commands and setting of the I
component.
U505
Source for setting value for I component
(2505)
0 = connector K0000
*
1 = connector K0001
S00
etc.
(B170)
U506
Source for control bit "Set I component"
(2506)
0 = binector B0000
*
1 = binector B0001
S00
etc.
(B170)
Technology controller: Output, limitation
U507
Source for variable positive limit
(2507)
After multiplication with U508, the contents of the selected connector act as
*
a positive limit for the technology controller output.
S00
0 = connector K0000
(B170)
1 = connector K0001
etc.
Note:
If the selected connector contains a negative value, a negative maximum
value is applied to the output of this limiter stage.
U508
Positive limit for output of technology controller
(2508)
See also U507
S00
FDS
(B170)
SIEMENS AG
6RX1700-0AD76
SIMOREG DC Master
Operating Instructions
Value range
[Unit]
Steps
All binector numbers
FB 114
1
0 to 1
FB 114
1
0 to 1
FB 114
1
0 to 1
FB 114
1
All connector
FB 114
numbers
1
All binector numbers
FB 114
1
All connector
FB 114
numbers
1
0.0 to 199.9
FB 114
[%]
0.1
Parameter list
No. indices
See
Factory
Change
setting
(Access /
Type
Status)
Ind: None
P052 = 3
FS=0
P051 = 40
Type: L2
Offline
Ind: 4
P052 = 3
FS=0
P051 = 40
Type: O2
Offline
Ind: 4
P052 = 3
FS=1
P051 = 40
Type: O2
Offline
Ind: 4
P052 = 3
FS=1
P051 = 40
Type: O2
Offline
Ind: None
P052 = 3
FS=0
P051 = 40
Type: L2
Offline
Ind: None
P052 = 3
FS=0
P051 = 40
Type: L2
Offline
Ind: None
P052 = 3
FS=1
P051 = 40
Type: L2
Offline
Ind: 4
P052 = 3
FS=100.0
P051 = 40
Type: O2
Online
11-143