7.7.10 Transmission of double-word connectors for technology and
communication modules
In the receive direction, the values of two adjacent connectors (K) are combined to form a single
double-word connector (KK) (e.g. K3002 and K3003 to KK3032). These double-word connectors
can themselves be connected to other function blocks in the usual way. For details of how to
connect double-word connectors, see Section 9.1, subsection, " The following rules apply to the
selection of double-word connectors ".
In the transmit direction, a double-word connector is applied by entering the same double-word
connector in two contiguous indices of the selection parameter.
Example:
7-60
U734
.01
32
K0032
.02
KK9498
9498
.03
KK9498
9498
.04
401
K0401
U734
.01
K0032
32
.02
KK9498
9498
.03
9499
KK9499
.04
401
K0401
Word
L-Word
2x the same KK - number
H-Word
Word
Word
H-Word
2 different KKs !
H-Word
Word
SIEMENS AG
SIMOREG DC Master
Operating Instructions
05.05