05.05
PNU
Description
11.86 Configuring the EB1 expansion board
U755
Signal type of analog inputs on EB1
(2755)
0 = Voltage input 0 to ± 10 V
1 = Current input 0 to ± 20 mA
*
(Z112)
i001: AI1 of the first EB1
(Z115)
i002: AI1 of the second EB1
U756
Normalization of analog inputs on EB1
(2756)
This parameter specifies the percentage value which is generated for an
input voltage of 10V (or an input current of 20mA) at the analog input.
(Z112)
The following general rule applies:
(Z115)
With a voltage input:
[%] =
U
756
10
With a current input:
[%] =
U
756
20
i001: AI1 of the first EB1
i002: AI2 of the first EB1
i003: AI3 of the first EB1
i004: AI1 of the second EB1
i005: AI2 of the second EB1
i006: AI3 of the second EB1
U757
Offset for analog inputs on EB1
(2757)
i001: AI1 of the first EB1
i002: AI2 of the first EB1
i003: AI3 of the first EB1
(Z112)
i004: AI1 of the second EB1
(Z115)
i005: AI2 of the second EB1
i006: AI3 of the second EB1
U758
Mode of signal injection at analog inputs on EB1
(2758)
0 = Injection of signal with sign
1 = Injection of absolute value of signal
*
2 = Injection of signal with sign, inverted
3 = Injection of absolute value of signal, inverted
(Z112)
(Z115)
i001: AI1 of the first EB1
i002: AI2 of the first EB1
i003: AI3 of the first EB1
i004: AI1 of the second EB1
i005: AI2 of the second EB1
i006: AI3 of the second EB1
U759
Source for selection of sign reversal at
analog inputs on EB1
(2759)
Selection of binector to control sign reversal at the analog input ("1" state
*
= reverse sign)
0 = binector B0000
(Z112)
1 = binector B0001
(Z115)
etc.
i001: AI1 of the first EB1
i002: AI2 of the first EB1
i003: AI3 of the first EB1
i004: AI1 of the second EB1
i005: AI2 of the second EB1
i006: AI3 of the second EB1
SIEMENS AG
6RX1700-0AD76
SIMOREG DC Master
Operating Instructions
Y
X .. input voltage in volts
V
X
Y .. % value which is generated for input
voltage X
Y
X .. input current in mA
mA
X
Y .. % value which is generated for input
current X
Value range
[Unit]
Steps
[SW 1.5 and later]
0 to 1
1
[SW 1.5 and later]
-1000.0 to 1000.0
[%]
0.1%
[SW 1.5 and later]
-100.00 to 100.00
[%]
0.01%
[SW 1.5 and later]
0 to 3
1
All binector numbers
[SW 1.5 and later]
1
Parameter list
No. indices
See
Factory
Change
setting
(Access /
Type
Status)
Ind: 2
P052 = 3
WE=0
P051 = 40
Typ: O2
on-line
Ind: 6
P052 = 3
WE=100,0
P051 = 40
Typ: I2
on-line
Ind: 6
P052 = 3
WE=0,00
P051 = 40
Typ: I2
on-line
Ind: 6
P052 = 3
WE=0
P051 = 40
Typ: O2
off-line
Ind: 6
P052 = 3
WE=0
P051 = 40
Typ: L2
off-line
11-165