11.63 Processing of connectors
Only active with optional technology software S00
Maximum selection
The largest of the input values selected by 3 indices each of the parameter (x1, x2, x3) is applied to the output.
U220
Source for maximum selection
(2220)
0 = Connector K0000
*
1 = Connector K0001
S00
etc.
(B140)
i001:
x1 Maximum selection 1 (FB 80, Output = K9193)
i002:
x2 Maximum selection 1
i003:
x3 Maximum selection 1
SW 1.8 and later:
i004:
x1 Maximum selection 2 (FB 174, Output = K9460)
i005:
x2 Maximum selection 2
i006:
x3 Maximum selection 2
i007:
x1 Maximum selection 3 (FB 175, Output = K9461)
i008:
x2 Maximum selection 3
i009:
x3 Maximum selection 3
i010:
x1 Maximum selection 4 (FB 176, Output = K9462)
i011:
x2 Maximum selection 4
i012:
x3 Maximum selection 4
Minimum selection
The smallest of the input values selected by 3 indices each of the parameter (x1, x2, x3) is applied to the output.
U221
Source for minimum selection
(2221)
0 = Connector K0000
*
1 = Connector K0001
S00
etc.
(B140)
i001:
x1 Minimum selection 1
i002:
x2 Minimum selection 1
i003:
x3 Minimum selection 1
SW 1.8 and later:
i004:
x1 Minimum selection 2
i005:
x2 Minimum selection 2
i006:
x3 Minimum selection 2
i007:
x1 Minimum selection 3
i008:
x2 Minimum selection 3
i009:
x3 Minimum selection 3
i010:
x1 Minimum selection 4
i011:
x2 Minimum selection 4
i012:
x3 Minimum selection 4
Tracking/storage elements
The tracking/storage elements are storage elements for the parameterized input quantity. The outputs are linked to connectors.
Transfer of the input quantity is controlled via the RESET, TRACK and STORE functions:
RESET:
When the controlling binector reaches log. "1", the output is set to 0.00% (y=0)
TRACK:
When the controlling binector reaches log. "1", the output is set to the input value and then tracks it continuously (y=x). If the
TRACK signal switches from "1" to "0", the last value applied to the y output is "frozen"
STORE: With a "0" to "1" transition of the controlling binector signal, the output is permanently set to the current input value (y=x). This
value then remains stored
Priority
1. RESET, 2. TRACK, 3. STORE
Tracking/storage element 1
U222
Source for input quantity (x)
(2222)
0 = connector K0000
*
1 = connector K0001
S00
etc.
(B145)
SIEMENS AG
6RX1700-0AD76
SIMOREG DC Master
Operating Instructions
(FB 81, Output = K9194)
(FB 177, Output = K9463)
(FB 178, Output = K9464)
(FB 179, Output = K9465)
Value range
[Unit]
Steps
FB 80, FB 174, FB 175, FB 176
All connector
numbers
1
FB 81, FB 177, FB 178, FB 179
All connector
numbers
1
All connector
FB 82
numbers
1
Parameter list
No. indices
See
Factory
Change
setting
(Access /
Type
Status)
Ind: 12
P052 = 3
FS=0
P051 = 40
Type: L2
off-line
Ind: 12
P052 = 3
FS=0
P051 = 40
Type: L2
off-line
Ind: None
P052 = 3
FS=0
P051 = 40
Type: L2
Offline