Modify parameter U099.001 using SET Single (for details in the shaded data area, see also
Section 7, Starting up PROFIBUS boards):
Byte
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Request identifier = 7063h (modify parameter value (array) U099), index = 0001h = 1d (bit 15 is
also set in the H byte in order to address the parameter number range from 2000 to 4000), value =
00C8h = 200d
Response by SIMOREG:
Byte
1
2
3
4
5
6
7
8
Response identifier = 0x4063, value of U099.001 = 00C8h = 200d (PWE2 remains unused
because SIMOREG 6RA70 has no double word parameters)
Information about PKW transmission:
The length of a request from the master is two words (for GET Single) or 4 words (SET Single).
The length of a SIMOREG response is always 3 words.
The low-order byte or word is always sent before the high-order byte or word.
The master may generate a new PKW request only after it has received a response from the slave
to the previous request.
The master identifies the response to the transmitted request by
evaluating the response identifier
evaluating the parameter number
evaluating the parameter value (if further identification is needed)
The CBD slave does not respond to a parameter request until it has received the relevant data
from the drive. The time delay depends on the type of request, but is at least 20 ms. During the
initialization phase after Power ON or a re-initialization operation due to a change in a CB
parameter setting, requests may not be processed at all, in which case the ensuing delay could be
as much as 40 s.
SIEMENS AG
6RX1700-0AD76
SIMOREG DC Master
Operating Instructions
DeviceNet identification
[FRAG] [XID] [SRC/DST MAC ID]
[Fragmentation Protocol]
[R/R] [Service]
Class
Instance
Attribute
PKE
IND
PWE1
PWE2
DeviceNet identification
[FRAG] [XID] [SRC/DST MAC ID]
[R/R] [Service]
PKE
PWE1
PWE2
0x10
[Set_Attribute_Single]
100
[PKW object] manufacturer-specific
1
[Instance number] always set to 1
1
[Attribute number] always set to 1
0x63
Parameter ID, L byte
0x70
Parameter ID, H byte
0x01
Parameter Index, L byte
0x80
Parameter Index, H byte
0xC8
Parameter value, L word, L byte
0x00
Parameter value, L word, H byte
0x00
Parameter value, H word, L byte
0x00
Parameter value, H word, H byte
0x90
[Set_Attribute_Single]
0x63
Parameter ID, L byte
0x40
Parameter ID, H byte
0xC8
Parameter value, L word, L byte
0x00
Parameter value, L word, H byte
0x00
Parameter value, H word, L byte
0x00
Parameter value, H word, H byte
Start-Up