PNU
Description
P494
Motor temperature analog 2 (temperature sensor at terminals 204 /
*
205): Tripping of alarm or fault message
FDS
Motor temperature grasped with KTY84
0
Monitoring deactivated
(G185)
1
Alarm (A029) at temperature > P491
2
Fault message (F029) at temperature > P492
3
Alarm (A029) at temperature > P491 and
fault message (F029) at temperature > P492
Motor temperature grasped with PTC thermistor
0
Monitoring deactivated
1
Alarm message (A029) when operating point of PTC thermistor
is reached
2
Fault message (F029) when operating point of PTC thermistor is
reached
3
Illegal setting
P495
Brush length sensing: Tripping of alarm or fault message
*
0
No brush length sensing (terminal 211 is not scanned)
FDS
1
Binary brush length sensing (terminal 211 is scanned)
Alarm (A025) in response to 0 signal
(G186)
2
Binary brush length sensing (terminal 211 is scanned)
Fault message (F025) in response to 0 signal
P496
Bearing condition: Tripping of alarm or fault message
*
0
No bearing condition sensing (terminal 212 is not scanned)
FDS
1
Bearing condition sensing (terminal 212 is scanned)
Alarm (A026) in response to 1 signal
(G186)
2
Bearing condition sensing (terminal 212 is scanned)
Fault message (F026) in response to 1 signal
P497
Air flow: Tripping of alarm or fault message
*
0
No air flow monitoring (terminal 213 is not scanned)
FDS
1
Air flow monitoring (terminal 213 is scanned)
Alarm (A027) in response to 0 signal
(G186)
2
Air flow monitoring (terminal 213 is scanned)
Fault message (F027) in response to 0 signal
P498
Temperature switch: Tripping of alarm or fault message
*
0
No temperature switch connected (terminal 214 is not scanned)
FDS
1
Temperature switch connected (terminal 214 is scanned)
Alarm (A028) in response to 0 signal
(G186)
2
Temperature switch connected (terminal 214 is scanned)
Fault message (F028) in response to 0 signal
11.28 Configuring of torque shell input
P500
Source for torque setpoint for slave drive
*
Selection of the connector to be injected as the torque setpoint for a slave
BDS
drive
(G160)
0 = connector K0000
1 = connector K0001
etc.
P501
Source for additional torque setpoint
*
Selection of connector to be injected as the additional torque setpoint
BDS
0 = connector K0000
(G160)
1 = connector K0001
etc.
SIEMENS AG
6RX1700-0AD76
SIMOREG DC Master
Operating Instructions
Value range
No. indices
[Unit]
Factory
Steps
setting
Type
0 to 3
Ind: 4
1
FS=0
Type: O2
0 to 2
Ind: 4
1
FS=0
Type: O2
0 to 2
Ind: 4
1
FS=0
Type: O2
0 to 2
Ind: 4
1
FS=0
Type: O2
0 to 2
Ind: 4
1
FS=0
Type: O2
All connector
Ind: 2
numbers
FS=170
1
Type: L2
All connector
Ind: 2
numbers
FS=0
1
Type: L2
Parameter list
See
Change
(Access /
Status)
P052 = 3
P051 = 40
Offline
P052 = 3
P051 = 40
Offline
P052 = 3
P051 = 40
Offline
P052 = 3
P051 = 40
Offline
P052 = 3
P051 = 40
Offline
P052 = 3
P051 = 40
Offline
P052 = 3
P051 = 40
Offline
11-55