Siemens 6RA7086-6KS22 Operating Instructions Manual page 591

6ra70 series, microprocessor-based converters from 6kw to 2500kw for variable-speed dc drives, simoreg dc master
Table of Contents

Advertisement

05.05
PNU
Description
Setpoint branching (output = K9234)
The input quantity is weighted with 2 parameters:
Parameter U297 determines the output value with an input = 0%
Parameter U298 determines the output value with an input = +100%
-U297 and -U298 apply in the case of negative input values.
The hysteresis set in parameter U299 is applied for transitions from negative to positive input values and vice versa
U296
Source for input quantity
(2296)
0 = connector K0000
*
1 = connector K0001
S00
etc.
(B161)
U297
Minimum speed
(2297)
S00
(B161)
U298
Maximum speed
(2298)
S00
(B161)
U299
Hysteresis
(2299)
S00
(B161)
11.65 Simple ramp-function generator
Only active with optional technology software S00
Please note: The output (y) = 0 is set in response to "Set simple ramp-function generator to zero" and POWER ON
The output (y) is frozen at the current value in response to "Stop simple ramp-function generator"
The ramp-up and ramp-down times are set to zero in response to "Bypass simple ramp-function generator"
Ramp-up integrator:
The simple ramp-function generator contains a flip-flop whose output is set to log. "0" (ramp generator initial run) after POWER
ON or when the ramp-function generator has been enabled. When the ramp-function generator output reaches a value
corresponding to the input quantity (y=x) for the first time, the flip-flop output switches to log. "1" and remains in this state until
the next enabling command. This output is linked to binector B9191. By parameterizing U301, index i001=919, it is possible to
apply this binector to the "Bypass simple ramp-function generator" function and thus to implement a ramp-up integrator
function.
U300
Source for input quantity
(2300)
0 = connector K0000
*
1 = connector K0001
S00
etc.
(B165)
U301
Source for control signals
(2301)
i001
Source for "Bypass simple ramp-function generator" signal
*
i002
Source for "Stop simple ramp-function generator" signal
S00
i003
Source for "Reset / enable simple ramp-function generator"
(B165)
signal
(0 = reset to zero, 1 = enable)
Settings:
0 = binector B0000
1 = binector B0001
etc.
U302
Ramp-up time
(2302)
S00
(B165)
U303
Ramp-down time
(2303)
S00
(B165)
SIEMENS AG
6RX1700-0AD76
SIMOREG DC Master
Operating Instructions
Value range
[Unit]
Steps
All connector
FB 112
numbers
1
FB 112 0.00 to 199.99
[%]
0.01
FB 112 0.00 to 199.99
[%]
0.01
FB 112 0.00 to 100.00
[%]
0.01
All connector
FB 113
numbers
1
All binector numbers
FB 113
1
FB 113 0.00 to 300.00
[s]
0.01
FB 113 0.00 to 300.00
[s]
0.01
Parameter list
No. indices
See
Factory
Change
setting
(Access /
Type
Status)
Ind: None
P052 = 3
FS=0
P051 = 40
Type: L2
Offline
Ind: None
P052 = 3
FS=0.00
P051 = 40
Type: O2
Online
Ind: None
P052 = 3
FS=100.00
P051 = 40
Type: O2
Online
Ind: None
P052 = 3
FS=0.00
P051 = 40
Type: O2
Online
Ind: None
P052 = 3
FS=0
P051 = 40
Type: L2
Offline
Ind: 3
P052 = 3
FS=
P051 = 40
i001: 0
Offline
i002: 0
i003: 1
Type: L2
Ind: None
P052 = 3
FS=0.00
P051 = 40
Type: O2
Online
Ind: None
P052 = 3
FS=0.00
P051 = 40
Type: O2
Online
11-127