05.05
PNU
Description
U049
OP1S operating display
(2049)
Function parameter for selecting parameters whose values must be
included in the operating display of the optional
OP1S convenience operator panel.
st
i001: 1
line on left
st
i002: 1
line on right
nd
i003: 2
line (actual value), visualization parameter only
rd
i004: 3
line (setpoint)
th
i005: 4
line
Connector type converters (only active with optional technology software S00)
2 connectors are converted into one double word connector.
st
U098
Operands for 1
(2098)
nd
Operands for 2
*
S00
i001:
Source for the low word of output connector KK9498
i002:
Source for the high word of output connector KK9498
(B151)
i003:
Source for the low word of output connector KK9499
i004:
Source for the high word of output connector KK9499
Settings:
0 = connector K0000
1 = connector K0001
etc.
11.56 Settable fixed values
Only active with optional technology software S00
U099
Fixed value
(2099)
The values set in Index .001 to .100 are connected to connectors K9501 to
S00
K9600
(B110)
11.57 Activation of fault messages and alarm messages
Only active with optional technology software S00
U100
Source for the activation of F023 and F019
(2100)
Selection of the binectors that activate fault messages F023 or F019 on log.
*
"1"
S00
0 = Binector B0000
(B115)
1 = Binector B0001
etc.
Up to SW 1.7: F023 (without fault value) if binector = 1 (FB 2)
SW 1.8 and later:
i001:
F023 with fault value 1 (FB 2)
i002:
F023 with fault value 2
i003:
F023 with fault value 3
i004:
F023 with fault value 4
i005:
F019 with fault value 1 (FB 286)
i006:
F019 with fault value 2
i007:
F019 with fault value 3
i008:
F019 with fault value 4
SIEMENS AG
6RX1700-0AD76
SIMOREG DC Master
Operating Instructions
connector type converter (result = KK9498)
connector type converter (result = KK9499)
Value range
[Unit]
Steps
[SW 1.9 and later]
0 to 3999
1
All connector
FB 298
numbers
FB 299
1
[SW 1.9 and later]
[SW 1.8 and later]
-199.99 to 199.99
[%]
0.01%
All binector numbers
FB 2, FB 286
1
Parameter list
No. indices
See
Factory
Change
setting
(Access /
Type
Status)
Ind:5
P052 = 3
FS=
P051 =40
i001: 19
on-line
i002: 38
i003: 25
i004: 28
i005: 59
Type: O2
Ind: 4
P052 = 3
FS=0
P051 = 40
Type: L2
off-line
Ind: 100
P052 = 3
FS=0.00
P051 = 40
Type: I2
on-line
Ind: 8
P052 = 3
FS=0
P051 = 40
Type: L2
off-line
11-103