Alarm
Alarm
ID
Severity
A27C-
MAJOR
02
A27C-
MAJOR
02
A27C-
MAJOR
02
A27C-
MAJOR
02
A27F-
CRITICA
01
L
A27F-
CRITICA
02
L
A280-
MAJOR
01
A280-
MAJOR
01
Issue 02 (2019-10-10)
Alarm
Probable Cause
Name
sensor is faulty.
Hot aisle 3
1. The cables to the temperature
temp/humid
and humidity sensor are loose or
sensor comm
damaged.
failed
2. The temperature and humidity
sensor is faulty.
Hot aisle 4
1. The cables to the temperature
temp/humid
and humidity sensor are loose or
sensor comm
damaged.
failed
2. The temperature and humidity
sensor is faulty.
Hot aisle 5
1. The cables to the temperature
temp/humid
and humidity sensor are loose or
sensor comm
damaged.
failed
2. The temperature and humidity
sensor is faulty.
Outdoor
1. The cables to the temperature
intake air 1
and humidity sensor are loose or
T/H sensor
damaged.
fault
2. The temperature and humidity
sensor is faulty.
Water
The water overflow sensor detects
overflow
water or the sensor is faulty.
alarm
Water
The water overflow sensor detects
overflow
water or the sensor is faulty.
alarm
Power
1. The power supply frequency is
frequency
below the lower threshold.
abnormal
2. The SPD and voltage detection
board is faulty.
Backup
1. The power supply frequency is
power
below the lower threshold.
frequency
2. The SPD and voltage detection
abnormal
board is faulty.
Copyright © Huawei Technologies Co., Ltd.
6 System Operation and Maintenance
Solution
temperature and humidity
sensor.
1. Check the cables to the
temperature and humidity
sensor.
2. Maintain or replace the
temperature and humidity
sensor.
1. Check the cables to the
temperature and humidity
sensor.
2. Maintain or replace the
temperature and humidity
sensor.
1. Check the cables to the
temperature and humidity
sensor.
2. Maintain or replace the
temperature and humidity
sensor.
1. Check the cables to the
temperature and humidity
sensor.
2. Maintain or replace the
temperature and humidity
sensor.
1. While configuring the water
overflow sensor, check and clear
the water source, and maintain
or replace the sensor.
1. While configuring the water
overflow sensor, check and clear
the water source, and maintain
or replace the sensor.
1. Check the power supply
frequency, and ensure that it is
within the working range.
2. Replace the SPD and voltage
detection board.
1. Check the power supply
frequency, and ensure that it is
within the working range.
2. Replace the SPD and voltage
detection board.