3.11 Precharging Refrigerant

Prerequisites
Before charging refrigerant, ensure that air is exhausted from the gas pipe connecting to the
refrigerant cylinder.
Context
Procedure
Step 1 Remove the vacuum pump from the vacuumizing equipment, and replace the vacuum pump
with a refrigerant cylinder, as shown in
Figure 3-31 Precharging refrigerant
(1) Refrigerant cylinder
Issue 02 (2019-10-10)
The NetCol8000 is a dual system, and charging refrigerant should be carried out one by
one or simultaneously. The following figure uses one system as an example.
Charge 8 kg refrigerant R410A for each system.
When charging refrigerant, you are advised to use a safety valve to prevent refrigerant
leakage during the removal of the leather hose, which may cause frostbite.
Wear antifreeze gloves when performing refrigerant-related operations.
Charge refrigerant (R410A) right after checking that the cooling system does not leak and
the vacuum level meets the requirements.
Copyright © Huawei Technologies Co., Ltd.
Figure
3-31.
(2) Electronic scale
3 Installation Guide
(3) Pressure gauge
47