Setting Teamwork Control Parameters - Huawei NetCol8000-E220 User Manual

Modular indirect evaporative cooling system
Hide thumbs Also See for NetCol8000-E220:
Table of Contents

Advertisement

NetCol8000-E220 Modular Indirect Evaporative Cooling
System
User Manual

4.4.4 Setting Teamwork Control Parameters

Prerequisites
Assign teamwork group number and teamwork unit address for the teamwork controlled
smart cooling products as follows:
Context
The parameters in this section are for reference only. Set actually parameter values as
required.
Procedure
Step 1 On the home screen, tap
shown in
Figure 4-17 Teamwork settings
Step 2 Set teamwork control parameters.
All teamwork control parameters can be set on the master smart cooling product. Only
Teamwork group No., Smart cooling product address, Enable teamwork CAN resistor,
Teamwork function and Networking mode can be set on slave smart cooling products.
Other parameters of the slave units will be modified by the master unit synchronously.
4-8
Table 4-8 Teamwork settings
Parameter
Teamwork
group No.
Issue 02 (2019-10-10)
Teamwork group no.: Group the smart cooling products in adjacent areas as one, that is,
assign one teamwork group number for them. At most four teamwork groups can be
assigned (1–4).
Teamwork unit address: The address for the smart cooling product in the same group
cannot be the same (address range: 1–32). The smart cooling product with minimum
address is the master one that collects, processes, and delivers data.
Figure
4-17.
describes how to set the parameters.
Description
The number of the
teamwork controlled group,
Copyright © Huawei Technologies Co., Ltd.
> Teamwork Settings, to enter Teamwork Settings page, as
Configuration
Principle
Set the assigned teamwork
control number.
4 Power-on and Commissioning
Default Value
1
Table
86