Removing The Transport Fasteners And Protective Covers - Huawei NetCol8000-E220 User Manual

Modular indirect evaporative cooling system
Hide thumbs Also See for NetCol8000-E220:
Table of Contents

Advertisement

NetCol8000-E220 Modular Indirect Evaporative Cooling
System
User Manual
Location
Hot aisle
----End
3.13 Removing the Transport Fasteners and Protective
Covers
Procedure
Step 1 Open the No. 2nd maintenance door. Loosen the three bolts on the compressor transport
fasteners using a 13# solid wrench.
Issue 02 (2019-10-10)
Display Name
Cold aisle 5
temp/humid
Hot aisle 1
temp/humid
Hot aisle 2
temp/humid
Hot aisle 3
temp/humid
Hot aisle 4
temp/humid
Hot aisle 5
temp/humid
The default addresses of T/H sensors purchased from Huawei are 1.
Keep the last RS485_R toggle switch at OFF.
After the addresses are set, power on the device. On the display's home screen, choose
Settings > System Settings > T/H Sensor, and set the sensors in the aisles corresponding
to the addresses to Enable. Otherwise, the sensors will not work.
Copyright © Huawei Technologies Co., Ltd.
Add
DIP Switch Sequence No.
ress
1
2
15
ON
ON
21
ON
OFF
22
OFF
ON
23
ON
ON
24
OFF
OFF
25
ON
OFF
3 Installation Guide
3
4
5
ON
ON
OFF
ON
OFF
ON
ON
OFF
ON
ON
OFF
ON
OFF
ON
ON
OFF
ON
ON
6
OFF
OFF
OFF
OFF
OFF
OFF
61