Huawei NetCol8000-E220 User Manual page 90

Modular indirect evaporative cooling system
Hide thumbs Also See for NetCol8000-E220:
Table of Contents

Advertisement

NetCol8000-E220 Modular Indirect Evaporative Cooling
System
User Manual
2.
Step 4 Add an SNMPv3 user.
1.
2.
Issue 02 (2019-10-10)
Figure 4-9 Setting read community
Tap the text box after Write Community, as shown in
Community as planned, tap
Figure 4-10 Setting write community
Tap Add under SNMP V3.
Enter a planned value for User Name, select values for Auth Protocol and Prop
Protocol from drop-down list boxes, and tap
MD5 and DES protocols are not secure. It is recommended that you set Auth Protocol
to SHA, and set Prop Protocol to AES. The following operations use the recommended
settings as an example.
Figure 4-11 Setting the protocol type
Copyright © Huawei Technologies Co., Ltd.
4 Power-on and Commissioning
Figure
and then tap Submit.
, as shown in
4-10. Set Write
Figure
4-11.
82