NetCol8000-E220 Modular Indirect Evaporative Cooling
System
User Manual
Figure 4-14 Setting SNMP port
Step 6 Tap Next Page.
Step 7 Set SNMP trap parameters.
1.
2.
3.
4.
5.
----End
Follow-up Procedure
After a USB flash drive has been inserted into the controller USB port and successfully
identified, tap Export File under MIB File to export the MIB file to the USB flash drive for
the customer's use in accessing a third-party EMS.
Issue 02 (2019-10-10)
SNMP Port is set to 161 by default.
Tap Add under SNMP Trap.
Set Trap Address as planned and Trap Port to the actual port number.
Trap Port is set to null by default.
Select the SNMP Version. If an SNMPv3 user is configured, it is recommended that
SNMP Version be set to SNMPv3.
If SNMP Version is set to SNMPv3, select an SNMPv3 user name, and then tap
as shown in
Figure
4-15.
Figure 4-15 Setting SNMP trap parameters
Tap Submit under SNMP Trap.
Copyright © Huawei Technologies Co., Ltd.
4 Power-on and Commissioning
Figure 4-16
shows successful file export.
84