Figure 3-48 Removing the transport fasteners from the compressor
Step 2 Remove the transport fasteners.
Step 3 Tighten the bolts on the compressor again to a torque of 12 N.m.
Step 4 Take out the two desiccant bags from No. 2nd maintenance door.
Step 5 Open the No. 1st maintenance door, and take out the one desiccant bags from No. 1st
maintenance door.
Step 6 Remove the air filter from the fresh air vent on the outdoor side and take out two desiccant
bags from the device.
Figure 3-49 Position of the desiccants
Issue 02 (2019-10-10)
Do not remove the bolts directly.
Put away the removed transport fasteners so that you can reinstall them if the indoor unit is to be
transported again in the container scenario.