NetCol8000-E220 Modular Indirect Evaporative Cooling
System
User Manual
Name
Spray
drainpipe
Condensat
e drainpipe
3.2.3 Pipe Support
Supports for pipes and water pipes as shown in the figure. The actual appearance of the
supports will be different based on onsite situations.
Figure 3-3 Pipe supports (unit: mm)
3.2.4 Cable
Waterproof connectors are designed based on the cable specifications recommended in the
table. If the cables used onsite are inconsistent with the recommended specifications, the
cables may fail to pass through waterproof connectors or the waterproof connectors cannot be
locked.
Issue 02 (2019-10-10)
Connector
G 1-1/2 inch
port with inner
screw threads
G 3/4 inch port
with inner
screw threads
The height of the U-shaped pipe clamp is 5 mm less than the pipe diameter (including the thermal
insulation foam).
Install a support every 2500 mm for the straight sections of pipes, and 1000 mm away from each
bending point in turning sections.
Copyright © Huawei Technologies Co., Ltd.
Pipe
Material
Dimensions
DN40
Rigid pipe:
made of PP-R,
C-PVC, or
other
materials
DN20
Rigid pipe:
made of PP-R,
C-PVC, or
other
materials
3 Installation Guide
Quantity
Length
engineerin
1
g survey.
2
22