Table 3-4 Cable terminal requirements
Item
Main power
supply
Standby power
supply
Cooling power
supply

3.3 (Optional) Concrete Platform Scenario

Prerequisites
The evenness of concrete platforms is critical to equipment installation. Ensure that the height
(altitude) difference of all platforms does not exceed 5 mm.
Context
Table 3-5 Hoisting Precautions
Stage
Before hoisting
Issue 02 (2019-10-10)
The cables are routed over a ladder or bracket in a single layer (E or F in IEC60364-5-523). The
distance between the cable and the cable is twice the diameter of the cable.
The ambient temperature is 30° C.
The AC voltage loss is less than 3%, and the DC voltage loss is less than 1%.
Single- or multi-core 90° C soft power cables with copper conductors are used.
It is recommended that AC power cables be no longer than 30 m.
Connection
Crimped OT
terminal
Crimped OT
terminal
Crimped OT
terminal
Precautions
Ensure that the crane and steel ropes provide the required bearing
capacity.
The doors of NetCol8000-Es to be hoisted are closed.
Ensure that the steel ropes are securely connected.
Ensure that the weather condition is good without wind when
NetCol8000-Es need to be hoisted outdoors.
Copyright © Huawei Technologies Co., Ltd.
Bolt
Torqu
Specifications
e
M10
26N.m
M10
26N.m
M10
26N.m
3 Installation Guide
Remarks
Standard configuration,
delivered with the
product
Standard configuration,
delivered with the
product
Standard configuration,
delivered with the
product