NetCol8000-E220 Modular Indirect Evaporative Cooling
System
User Manual
Alarm
Alarm
ID
Severity
A28C-
CRITICA
04
L
A28C-
CRITICA
08
L
A28C-
CRITICA
08
L
Issue 02 (2019-10-10)
Alarm
Probable Cause
Name
8. The exhaust fan is faulty.
Comp 2 high
1. The input power of the outdoor
discharge
unit has an open phase, incorrect
pressure
phase sequence, or is unavailable.
alarm
2. Cables to the indoor or outdoor
fan are not properly connected.
3. The condenser fins are dirty or
blocked.
4. The outdoor fan or its drive is
faulty.
5. The cables to the high pressure
switch are loose or damaged.
6. The high pressure switch is
faulty.
7. The refrigerant is overfilled.
8. The exhaust fan is faulty.
Comp 1 high
1. The input power of the outdoor
discharge
unit has an open phase, incorrect
pressure
phase sequence, or is unavailable.
alarm
2. Cables to the indoor or outdoor
fan are not properly connected.
3. The condenser fins are dirty or
blocked.
4. The outdoor fan or its drive is
faulty.
5. The cables to the high pressure
switch are loose or damaged.
6. The high pressure switch is
faulty.
7. The refrigerant is overfilled.
8. The exhaust fan is faulty.
Comp 2 high
1. The input power of the outdoor
discharge
unit has an open phase, incorrect
pressure
phase sequence, or is unavailable.
alarm
2. Cables to the indoor or outdoor
fan are not properly connected.
3. The condenser fins are dirty or
blocked.
4. The outdoor fan or its drive is
faulty.
5. The cables to the high pressure
switch are loose or damaged.
6. The high pressure switch is
Copyright © Huawei Technologies Co., Ltd.
6 System Operation and Maintenance
Solution
exhaust fan.
1. Check the input power of the
outdoor unit.
2. Check the cables to the indoor
and outdoor fans.
3. Clean the condenser fins.
4. Maintain or replace the
outdoor fan or its drive.
5. Check cables to the high
pressure switch.
6. Maintain or replace the high
pressure switch.
7. Decrease certain amount of
refrigerant.
8. Maintain or replace the
exhaust fan.
1. Check the input power of the
outdoor unit.
2. Check the cables to the indoor
and outdoor fans.
3. Clean the condenser fins.
4. Maintain or replace the
outdoor fan or its drive.
5. Check cables to the high
pressure switch.
6. Maintain or replace the high
pressure switch.
7. Decrease certain amount of
refrigerant.
8. Maintain or replace the
exhaust fan.
1. Check the input power of the
outdoor unit.
2. Check the cables to the indoor
and outdoor fans.
3. Clean the condenser fins.
4. Maintain or replace the
outdoor fan or its drive.
5. Check cables to the high
pressure switch.
6. Maintain or replace the high
pressure switch.
7. Decrease certain amount of
149