Huawei NetCol8000-E220 User Manual page 81

Modular indirect evaporative cooling system
Hide thumbs Also See for NetCol8000-E220:
Table of Contents

Advertisement

NetCol8000-E220 Modular Indirect Evaporative Cooling
System
User Manual
Menu
Settings > Quick
Settings > T/H
Settings
Issue 02 (2019-10-10)
Parameter
Temperature
and humidity
control type
Temperature
setpoint
Copyright © Huawei Technologies Co., Ltd.
4 Power-on and Commissioning
Setting Guide
generated, port 1 for
reporting common
alarms generates a dry
contact close alarm; if a
major alarm is generated,
port 2 for reporting
common alarms
generates a dry contact
close alarm.
When DO associated is
set to Alarm & startup
status, if a alarm is
generated, the dry
contact of common alarm
1 is open. If a startup
status is generated, the
dry contact of common
alarm 2 is close. If a
shutdown status is
generated, the dry
contact of common alarm
2 is open.
When DO associated
alarm is set to No, ports
1 and 2 for reporting
common alarms are open
and generate no alarms.
When the application
scenario is cold or hot
aisle containment, you
are advised to choose
Cold aisle if the cold
aisle T/H sensors are
configured, and choose
Supply air if the cold
aisle T/H sensors are not
configured.
When the application
scenario is non-aisle
containment, you are
advised to choose
Return air, and choose
Cold aisle if the cold
aisle T/H sensors are
configured.
Hot aisle is not
recommended.
After the Temperature and
humidity control type and
the temperature value under
Default Value
Return air
25º C
73