Replacing The Switch - Huawei NetCol8000-E220 User Manual

Modular indirect evaporative cooling system
Hide thumbs Also See for NetCol8000-E220:
Table of Contents

Advertisement

NetCol8000-E220 Modular Indirect Evaporative Cooling
System
User Manual
2.
Step 4 Install a new spray pump on the device, install the flange assembly at the inlet and outlet of
the water pump, and close the maintenance door.
Step 5 After powering on the device, choose Maintenance > Performance Maintenance on the
home screen to clear the running time of the spray pump.
Step 6 Tap Startup on the home screen. Ensure that the device is running normally without any
alarms.
----End

6.5.8 Replacing the Switch

Prerequisites
Procedure
Step 1 On the controller home screen, tap Shutdown, and turn off the device switch in the PDC.
Issue 02 (2019-10-10)
Figure 6-11 Removing the flange assembly
Remove the fastener from the water pump using a socket wrench, and pull out the spray
pump.
The switch needs to be replaced.
A spare switch is available and functional.
Tool: Phillips screwdriver
Copyright © Huawei Technologies Co., Ltd.
6 System Operation and Maintenance
(Figure 3-32
shows the position of switch.)