Starting The Drive Locally - ABB ACS5000 User Manual

Medium voltage ac drive air-cooled, 2 - 7 mva
Hide thumbs Also See for ACS5000:
Table of Contents

Advertisement

ABB
8.6.3

Starting the drive locally

5k A UM
1
Enable the local control mode of the CDP control panel.
2
This step only applies to drives which are equipped with the optional
safety relay.
3
If the EMERGENCY-OFF RESET pushbutton is flashing, press the
EMERGENCY-OFF RESET pushbutton to cancel flashing.
Each time the auxiliary voltage is switched off and on again, the emer-
gency-off safety relay of the drive is actuated and lets the EMER-
GENCY-OFF RESET pushbutton flash.
The EMERGENCY-OFF RESET pushbutton also flashes if the
EMERGENCY-OFF pushbutton on the control compartment door, or
any other emergency-off switch linked to the drive, is pressed. If the
EMERGENCY-OFF RESET pushbutton continues flashing, verify
that there is no emergency-off command active.
For further information, see
4
Check that no alarm or fault messages are displayed on the CDP
control panel.
When a fault message is displayed on the CDP control panel, reset
the fault.
If a fault cannot be reset, it must be rectified by the responsible
personnel.
For further information, see
When no alarms and faults are present and the drive is ready, the
CDP control panel displays ReadyOn:
1 L ->
StateINU
MOTOR SP
POWER
5
Press the SUPPLY ON pushbutton on the control compartment door
to charge the DC link. The SUPPLY ON pushbutton flashes while the
DC link is charged.
3BHS221906 ZAB E01 Rev. D
8.8
Emergency-off.
10.3 Alarm / fault
0.0 rpm
ReadyOn
0.00 rpm
0.0 kW
Chapter 8 - Operation
indications.
8-9 (14)