Disabling / Enabling Local Lock Function - ABB ACS5000 User Manual

Medium voltage ac drive air-cooled, 2 - 7 mva
Hide thumbs Also See for ACS5000:
Table of Contents

Advertisement

ABB
9.8.3

Disabling / enabling local lock function

Enabling the local lock
Disabling the local lock
5k A UM
Accidental switching from remote control to local control can be prevented
with the local lock function.
The corresponding parameter is 16.04 LOCAL LOCK and belongs to the
parameter group 16 SYSTEM CTRL INPUTS.
To enable the local lock, set parameter 16.04 to 2 (LOCKED).
With this parameter setting, local control (including the LOC-REM key) is
disabled.
If the CDP control panel or a DriveWindow PC is in local control mode at
the time that the local lock is enabled, they remain in local control mode
until they are switched to remote control mode. This means that the CDP
control panel displays the letter L until you press the LOC-REM key.
To disable the local lock, set parameter 16.04 to 1 (OPEN). With this
parameter setting, switching between remote and local control is enabled.
3BHS221906 ZAB E01 Rev. D
Chapter 9 - CDP control panel
9-21 (24)