Checks Before Starting The Drive; Starting The Drive From Remote - ABB ACS5000 User Manual

Medium voltage ac drive air-cooled, 2 - 7 mva
Hide thumbs Also See for ACS5000:
Table of Contents

Advertisement

Chapter 8 - Operation
8.6.1

Checks before starting the drive

8.6.2

Starting the drive from remote

8-8 (14)
DANGER
Hazardous voltages!
All covers must be screwed in place to prevent unintentional contact with
energized components.
The manual release of the safety switch must be in the locked position to
prevent the door of the medium voltage compartment being opened
unintentionally during operation.
When the drive system is put into service after it has been commissioned,
or after it has been taken out of service for a longer period, check the drive
according to the following list:
Check that no tools and foreign objects are left inside the cabinet.
Check that all auxiliary power supplies from external sources are
switched on.
Check that all internal circuit breakers of the drive are closed.
Check that all covers are mounted and the doors are closed, locked
and / or bolted.
Check that the grounding switch is in position not grounded.
Check that the MCB is in operating position.
Check that there is no run interlock active.
When the drive is operated from remote through a higher-level control
system, or an operator control desk, follow the instructions in the
appropriate manuals.