Drive With Non-Integrated Transformer; Fig. 6-3 Drive With Non-Integrated Transformer - ABB ACS5000 User Manual

Medium voltage ac drive air-cooled, 2 - 7 mva
Hide thumbs Also See for ACS5000:
Table of Contents

Advertisement

Chapter 6 - Electrical installation
6.5.2

Drive with non-integrated transformer

6-4 (22)
1
1
Transformer
2
Terminal compartment
3
Drive
Fig. 6-3
Drive with non-integrated transformer
Cabling includes the following connections between the drive and the
transformer:
Transformer secondary cables
Cable from the PT100 temperature sensor in the transformer cabinet
Cable for the start command of the transformer fan units. Cooling fan
configurations with a stand-by unit require a separate cable for the
stand-by unit.
Cable for several alarm and trip signals from transformer protection
relays, cooling fans, air filter and air pressure monitoring
Optional power supply cable for the heating cable of the transformer
For information on each individual connection, see
diagrams.