ABB ACS5000 User Manual page 85

Medium voltage ac drive air-cooled, 2 - 7 mva
Hide thumbs Also See for ACS5000:
Table of Contents

Advertisement

ABB
Bolted connections
Material requirements
Connection type
Lubrication
Tightening torque
5k A UM
Use stainless steel bolts and nuts with the appropriate steel grade and
property class for the connection (recommended: A2-70 [designation
according to ISO 3506]).
Nuts with bonded coating can be used as an alternative to uncoated
stainless steel nuts.
The following connection type is recommended when a cable lug
12: 4)
is connected to a busbar:
Spring washer
(Fig. 6-12: 1)
side of the busbar
Other washers can be used, provided they maintain the required
contact pressure.
Fig. 6-12
Bolted busbar connection
Use cable lugs suitable for M12 bolts.
If stainless steel bolts and nuts are used, lubricate the thread and
head contact surface of the bolt using recommended pastes, eg,
MOLYKOTE D paste.
If a coated nut (eg, with bonded molybdenum-disulfide [MoS
coating) is used, the connection does not have to be lubricated.
Tighten bolted connections with bolts of sizes M10 and greater with
the recommended nominal torque for the bolt size used.
3BHS221906 ZAB E01 Rev. D
and flat washer
(Fig. 6-12: 3).
1
2
3
2
Chapter 6 - Electrical installation
(Fig. 6-
(Fig. 6-12: 2)
on each
1
4
]
2
6-15 (22)