ABB ACS5000 User Manual page 159

Medium voltage ac drive air-cooled, 2 - 7 mva
Hide thumbs Also See for ACS5000:
Table of Contents

Advertisement

ABB
5k A UM
If the DC link is discharged, the message ReadyOn is displayed on
the CDP control panel.
1 L ->
StateINU
MOTOR SP
POWER
If the DC-link voltage does not decrease below 50 V, do not continue
but call ABB. To contact the ABB service organization, see
information.
3
To test the lamp GROUNDING SWITCH UNLOCKED, activate the
lamp test with parameter 16.7.
(For information on setting parameters, see
If the lamp does not light up, replace it.
If the lamp lights up after it was replaced, continue with step 7.
If the lamp does not light up after it was replaced, continue with
step 4.
4
Verify that the MCB (main circuit breaker) is open.
1
If the MCB is open, check that it is locked out.
2
Check if the SUPPLY OFF lamp is lit.
When the lamp is lit, the feedback signal "main circuit breaker
open" is present at digital input DI14 of I/O module A2531.
5
Check if the LED of digital output DO07 (I/O module A2541) is lit.
When the LED is lit, the grounding switches are released.
6
Switch off the circuit breaker (Q1002) for the charging transformer.
This prevents hazardous charging voltages being fed into the drive.
7
Carefully turn the grounding switches to the grounded position if it has
been verified:
that hazardous voltages cannot be fed into the drive from the
main power supply or the motor,
that the DC link is discharged,
that the grounding switches are released (DO07 is energized).
that the drive status is ReadyOn.
8
If you cannot turn the grounding switches, continue with
gency release of the door safety
3BHS221906 ZAB E01 Rev. D
Chapter 10 - Preventive and corrective maintenance
600.0 rpm
ReadyOn
0.00 rpm
0.0 kW
switch.
Contact
9.6 Parameters
mode.)
10.6.6 Emer-
10-23 (36)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents