Operating conditions
The operating conditions for the drive are based on IEC 60721-3-3 'Stationary use at weather-
protected locations' (unless indicated otherwise).
3K3 Climatic conditions
Air temperature
Relative humidity
Absolute humidity
Condensation
3B1 Biological conditions
Flora
Fauna
3C2 Chemically active substances
Sea salt and road salts
Sulphur dioxide
Hydrogen sulfide
Chlorine
Hydrogen chloride
Hydrogen fluoride
Ammonia
Ozone
Nitrogen oxides
3S2 Mechanically active substances
Sand
Dust (suspension)
Dust (sedimentation)
3M1 Mechanical conditions
Stationary vibration sinusoidal
■ Displacement amplitude
■ Acceleration amplitude
Non-stationary vibration (including shock)
■ Shock response spectrum
a.
5 – 95% in the absence of condensation
5 – 60% in the presence of corrosive gases
If the operating conditions are not within the specifications, contact ABB.
5k A UM
a
3BHS221906 ZAB E01 Rev. D
5 – 40 °C
5 – 85%
3
1 – 25 g/m
No
No
No
Salt mist
Mean value
3
0.3 mg/m
3
0.1 mg/m
3
0.1 mg/m
3
0.1 mg/m
3
0.01 mg/m
3
1 mg/m
3
0.05 mg/m
3
0.5 mg/m
3
30 mg/m
3
0.2 mg/m
3
1.5 mg/m
0.3 mm (2 – 9 Hz)
2
1 m/s
(9 – 200 Hz)
2
40 m/s
Max. value
3
1.0 mg/m
3
0.5 mg/m
3
0.3 mg/m
3
0.5 mg/m
3
0.03 mg/m
3
3 mg/m
3
0.1 mg/m
3
1.0 mg/m