Connecting A Grounding Set - ABB ACS5000 User Manual

Medium voltage ac drive air-cooled, 2 - 7 mva
Hide thumbs Also See for ACS5000:
Table of Contents

Advertisement

Chapter 10 - Preventive and corrective maintenance
10.6.5

Connecting a grounding set

10-24 (36)
9
Switch off and lockout all auxiliary voltages from external sources.
10 Verify that the drive system is de-energized.
11 Ground the drive with a grounding set (option).
3
2
1
1
Telescopic insulating pole
2
Enclosure ground clamp
3
Busbar ground clamp
Fig. 10-8
Four-way grounding set (option)
1
Connect the enclosure grounding clamp
ball stud of the cabinet's grounding frame.
2
Use the telescopic insulating pole to connect the busbar ground
clamps
(Fig. 10-8: 3)
tighten each connection.
The drive is now dead, and safe access is possible.
3BHS221906 ZAB E01 Rev. D
(Fig. 10-8: 2)
to the ground ball studs of the busbars, and to
ABB
to the ground
5k A UM

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents