Cabling Between Drive And Transformer; Drive With Integrated Transformer; Fig. 6-2 Drive With Integrated Transformer - ABB ACS5000 User Manual

Medium voltage ac drive air-cooled, 2 - 7 mva
Hide thumbs Also See for ACS5000:
Table of Contents

Advertisement

ABB
6.5

Cabling between drive and transformer

6.5.1

Drive with integrated transformer

5k A UM
1
1
Transformer
2
Terminal compartment
3
Drive
Fig. 6-2
Drive with integrated transformer
Cabling of a standard drive configuration includes the following
connections between the drive and the transformer:
Transformer secondary cables
Auxiliary power supply for the two transformer protection relays
Cable to the solenoid door lock in the transformer cabinet
Cable from the PT100 temperature sensor in the transformer cabinet
Three-phase power supply cable to each of the transformer fan units
Cable for several alarm and trip signals from transformer protection
relays, cooling fans, air filter and pressure monitoring
Heating cable from the drive control compartment to the transformer
cabinet (option)
FE busbars of transformer and drive cabinet
All cables are prepared for connection. Power cables are rolled up in the
transformer cabinet, control cables in the drive cabinet.
The cables can be identified by their specific number and are labeled with
the designation of the terminal where they are connected to.
For information on each individual connection, see
diagrams.
3BHS221906 ZAB E01 Rev. D
Chapter 6 - Electrical installation
2
3
Appendix D – Wiring