Chapter 6 - Electrical installation
6.7.3

Connecting the cables

Connecting the cables
Checking the cable insulation
Drive with integrated transformer
6-12 (22)
NOTICE
Risk of flashover!
High voltages will be present in the terminal compartment. High voltages
can cause a flashover between conductors with different electric potential,
and between a conductor and earth.
Therefore, maintain a minimum clearance of 55 mm between a conductor
and the terminals of any other conductor, and between a conductor and
earth.
Measure the insulation resistance of each cable before connecting it
and verify that the results are within the specification of the cable
manufacturer
Leave the conductors unconnected at both ends until the
commissioning personnel has given permission.
Connect the primary and secondary cables of the transformer, and
the motor cables to their corresponding busbars.
Connect the primary cables of the transformer to the side of the
busbars where the arrows point to in
Orientate the bolts for the transformer primary cables as shown in
6-7.
Fig. 6-7
Cable connection and bolt orientation
3BHS221906 ZAB E01 Rev. D
Fig.
6-7.
ABB
Fig.
5k A UM