Storage; Storage Conditions - ABB ACS5000 User Manual

Medium voltage ac drive air-cooled, 2 - 7 mva
Hide thumbs Also See for ACS5000:
Table of Contents

Advertisement

Chapter 4 - Transportation, storage and disposal
4.5

Storage

4.5.1

Storage conditions

4.5.2
Storage
4-4 (6)
The minimum requirements for storage are based on IEC 60721-3-1
'Classification of environmental conditions: Classification of groups of
environmental parameters and their severities; Storage'.
1K4 Climatic conditions
Air temperature
Relative humidity
Absolute humidity
1Z3 Special climatic conditions
Movement of surrounding air
1B1 Biological conditions
Flora
Fauna
1M3 Mechanical conditions
Vibration
■ Displacement amplitude
■ Acceleration amplitude
The drive can be stored for up to one year in the original packaging as long
as it is not damaged or opened. For information on longer storage periods,
contact the ABB service organization.
If the drive is taken out of service for a longer time, proceed as follows:
1
Cover all cable inlets and ventilation slots with an impermeable plastic
or aluminum foil and a wooden panel.
2
Add a desiccant of the appropriate quality:
1 unit desiccant (30 g) absorbs 6 g water vapor.
The following quantity is needed when using a polyethylene foil:
2
10 units/m
3
Close and lock the doors of the cabinet.
4
Use polyethylene or equivalent for packaging:
2
0,3 g/m
/24h water vapor diffusion
5
Attach humidity indicators to the packaging.
3BHS221906 ZAB E01 Rev. D
foil
ABB
-25 – +55 °C
5 – 100%
0.5 – 29%
30 m/s
Negligible
Negligible
3 mm (2 – 9 Hz)
2
10 m/s
(9 – 200 Hz)
5k A UM

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents